Rated voltage (kV) | 40.5 | 72.5 | 126 | 252 | 550 | 800 | |
Rated current (A) |
1600/ 2000 |
3150 | 3150 | 4000 | 5000 | 6300 | |
Rated short circuit breaking current (kA) | 25/31.5 | 40 | 40 | 50 | 63 | 63 | |
Rated short time withstand current/duration (kA/s) |
25/4 31.5/4 |
40/4 | 40/4 | 50/3 | 63/3 | 63/3 | |
Rated peak withstand current (kA) | 63/80 | 100 | 100 | 125 | 160 | 171 | |
Rated power frequency withstand voltage (kV) | To earth | 95 | 350 | 230 | 460 | 740 | 960 |
Between open contacts | 118 | 410 |
230+ 70 |
460+ 145 |
740+ 315 |
960+ 462 |
|
Rated lightning impulse withstand voltage (kV) | To earth | 185 | 160 | 550 | 1050 | 1675 | 2100 |
Between open contacts | 215 | 200 |
550+ 100 |
1050+ 200 |
1675+ 450 |
2100+ 650 |
|
Rated switching impulse withstand voltage (kV) | To earth | 1300 | 1550 | ||||
Between open contacts |
1175+ 450 |
1425+ 650 |
|||||
Mechanical life (times) | 10000 | 10000 | 10000 | 10000 | 10000 |